14.4.9.3
Function block
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
IEC10000248-2-en.vsd
GOOSESPRCV
BLOCK
^SRCSPOUT
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248 V2 EN-US
Figure 257:
GOOSESPRCV function block
14.4.9.4
Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the
Engineering Manual
.
PID-6832-INPUTSIGNALS v3
Table 409:
GOOSESPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCSPOUT
BOOLEAN
0
Source to single point output
PID-6832-OUTPUTSIGNALS v3
Table 410:
GOOSESPRCV Output signals
Name
Type
Description
SPOUT
BOOLEAN
Single point output
DATAVALID
BOOLEAN
Data valid for single point output
COMMVALID
BOOLEAN
Communication valid for single point output
TEST
BOOLEAN
Test output
14.4.9.5
Settings
PID-6832-SETTINGS v3
Table 411:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
14.4.9.6
Operation principle
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
535
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...