Operation
counter
Alarm limit
Check
NOOPER
OPERALM
OPERLO
IEC12000617 V2 EN-US
Figure 214:
Functional module diagram for circuit breaker operation cycles
Operation counter
The operation counter counts the number of operations based on the state of change
of the auxiliary contact inputs
POSCLOSE
and
POSOPEN
.
The number of operations NOOPER is given as a service value. The old circuit
breaker operation counter value can be used by adding the value to the
InitCounterVal
parameter and can be reset by
Clear CB wear
in the Clear menu on
the LHMI or activating the input
RSTCBWR
.
Alarm limit check
OPERALM
is generated when the number of operations exceeds the set value of the
OperAlmLevel
threshold setting.
If the number of operations increases and exceeds the limit value set with the
OperLOLevel
setting, the
OPERLO
output is activated.
The binary outputs
OPERALM
and
OPERALO
are deactivated when the
BLKALM
input is activated.
11.4.7.6
Circuit breaker operation monitoring
GUID-6DAE4C6B-BD66-49CD-817D-08E4EBF47DE0 v9
The circuit breaker operation monitoring subfunction indicates the inactive days of
the circuit breaker and gives an alarm when the number of days exceed the set
level. The operation of the circuit breaker operation monitoring is shown in figure
POSCLOSE
POSOPEN
BLOCK
BLKALM
Inactive timer
Alarm limit
Check
INADAYS
MONALM
IEC12000614 V2 EN-US
Figure 215:
Functional module diagram for circuit breaker operation monitoring
Section 11
1MRK 505 384-UEN A
Monitoring
444
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...