PID-6829-INPUTSIGNALS v3
Table 403:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCINTOUT
INTEGER
0
Source to integer output
PID-6829-OUTPUTSIGNALS v3
Table 404:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
14.4.7.5
Settings
PID-6829-SETTINGS v3
Table 405:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
14.4.7.6
Operation principle
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
Freeze
0
1
0
Incoming data with q=Invalid
Freeze
0
1
0
Incoming data with q=test
Freeze
0
1
1
Incoming data with q=test+oldData
Freeze
0
1
1
Receiver in block
Freeze
0
1
0
Receiver in block and communication
error
Freeze
0
0
0
Table continues on next page
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
531
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...