PulseTime
Ondelay
OUTPUT 1
PulseTime
Ondelay
OUTPUT 2
PulseTime
Ondelay
OUTPUT 3
INPUT 17
INPUT 32
INPUT 1
INPUT 16
IEC09000612-3-en.vsd
³
1
³
1
³
1
³
1
&
&
&
&
&
&
³
1
³
1
t
t
t
Offdelay
t
t
t
t
Offdelay
t
Offdelay
t
ModeOutput1=Pulsed
ModeOutput2=Pulsed
ModeOutput3=Pulsed
IEC09000612 V3 EN-US
Figure 167:
Trip matrix internal logic
Output signals from TMAGAPC are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time shall be set to at least 0.150 seconds in order to obtain
satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
10.3.7
Technical data
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 209:
Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TMAGAPC
6
6
-
10.4
Logic for group alarm ALMCALH
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
10.4.1
Identification
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group alarm
ALMCALH
-
-
Section 10
1MRK 505 384-UEN A
Logic
346
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...