Name
Values (Range)
Unit
Step
Default
Description
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step2
(Instantaneous / IEC / ANSI)
tReset2
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 2
tPCrv2
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 2
tACrv2
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 2
tBCrv2
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 2
tCCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 2
tPRCrv2
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 2
tTRCrv2
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step 2
tCRCrv2
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 2
IN3>Min
1 - 2500
%IB
1
1
Minimum used operate residual current
level for step 3 in % of IBase, if IN3> is
less than IN3>Min then IN3> is set to
IN3>Min
IN3>Max
1 - 2500
%IB
1
2500
Maximum used operate residual current
level for step 3 in % of IBase, if IN3> is
greater than IN3>Max then IN3> is set to
IN3>Max
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step3
(Instantaneous / IEC / ANSI)
tReset3
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 3
tPCrv3
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 3
tACrv3
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 3
tBCrv3
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 3
tCCrv3
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 3
tPRCrv3
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 3
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 3
IN4>Min
1 - 2500
%IB
1
1
Minimum used operate residual current
level for step 4 in % of IBase, if IN4> is
less than IN4>Min then IN4> is set to
IN4>Min
Table continues on next page
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
111
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...