Name
Type
Description
LIMIT2
BOOLEAN
Counted value is larger than or equal to
CounterLimit2
LIMIT3
BOOLEAN
Counted value is larger than or equal to
CounterLimit3
LIMIT4
BOOLEAN
Counted value is larger than or equal to
CounterLimit4
VALUE
INTEGER
Counted value
11.9.6
Settings
PID-6966-SETTINGS v2
Table 363:
L4UFCNT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
CountType
Positive edge
Negative edge
Both edges
-
-
Positive edge
Select counting on positive and/or
negative flanks
CounterLimit1
1 - 65535
-
1
100
Value of the first limit
CounterLimit2
1 - 65535
-
1
200
Value of the second limit
CounterLimit3
1 - 65535
-
1
300
Value of the third limit
CounterLimit4
1 - 65535
-
1
400
Value of the fourth limit
MaxValue
1 - 65535
-
1
500
Maximum count value
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
-
-
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or
pulsed overflow flag
InitialValue
0 - 65535
-
1
0
Initial count value after reset of the
function
11.9.7
Monitored data
PID-6966-MONITOREDDATA v2
Table 364:
L4UFCNT Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
INTEGER
-
-
Counted value
11.9.8
Technical data
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 365:
L4UFCNT technical data
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
Section 11
1MRK 505 384-UEN A
Monitoring
486
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...