CBREADY
CBCLOSED
IEC04000199-3-en.vsd
t1 1Ph
t2 3Ph
tReclaim
Fault
UNSUCCL
3PT2
3PT1
1PT1
INPROGR
READY
SYNC
TR3P
START
PREP3P
CLOSECB
IEC04000199 V3 EN-US
Figure 119:
Permanent single-phase fault, single-phase trip, two-shot
reclosing, ARMode=1ph + 1*2ph
9.2.7
Technical data
M12379-1 v13
Table 151:
SMBRREC technical data
Function
Range or value
Accuracy
Dead time:
shot 1 “t1 1Ph”
shot 1 “t1 2Ph”
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
(0.000-120.000) s
±0.2% or ±35 ms
whichever is greater
Dead time:
shot 2 “t2 3Ph”
shot 3 “t3 3Ph”
shot 4 “t4 3Ph”
shot 5 “t5 3Ph”
(0.00-6000.00) s
±0.2% or ±35 ms
whichever is greater
Extend three-phase dead time duration
“tExtended t1”
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be
closed before new sequence is allowed
“tCBClosedMin”
(0.00-6000.00) s
±0.2% or ±35 ms
whichever is greater
Wait time for the slave to close when WAIT
input has reset “tSlaveDeadTime”
(0.100-60.000) s
±0.2% or ±35 ms
whichever is greater
Maximum allowed start pulse duration
“tLongStartInh”
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
Circuit breaker closing pulse duration
“tPulse”
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
Table continues on next page
1MRK 505 384-UEN A
Section 9
Control
Breaker protection REQ650 2.2 IEC
265
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...