12
192.168.50.52/
EN/11.2018/G67C © STULZ GmbH – all rights reserved
wib8000 original instructions
5. Configuration
A password with administrator authorization for the first access is printed on the adhesive label.
After you have entered the password and confirmed it by Enter/Return the authorization is shown for a short
time.
Special case: Chiller with C6000
To get a
for a chiller (CSO, CLO, CSI, CPI), equipped with a C6000 controller, introduce the password of the C6000 con-
trol level in the menu Config/Web Interface.
You installed the Stulz bus by connecting the controllers by means of bus lines and setting the global address-
es. You also linked the WIB8000 module in the Stulz bus and supplied it with power.
Before you connect the WIB8000 with the customer network, it is necessary to adjust the network parame-
ters which are provided by the customer. For this connect the WIB8000 to your PC/laptop first and configure
the WIB. The adjusted parameters are updated after a WIB8000 reboot.
To connect the WIB8000 to your PC/laptop the following network parameters are adjusted as default
settings:
DHCP: off
IP address: 192.168.50.52
Subnet mask: 255.255.255.0
Important: If the settings which are desired by the customer differ from the settings above, you can not reach
the WIB8000 anymore by your PC/laptop after a reboot. It has now been set up for the customer network.
Now you can switch on the PC, which also provides a network connection, start the internet browser and call
the html pages stored in the WIB module by typing the address http://192.168.50.52 into the command line.
Via the html pages you can configure the WIB module.
First you are asked to enter the password. Three passwords for different authorizations exist:
1.
............... (highest authorization, administrator)
2.
............... (medium authorization, read and write, only levels "Info" and "Operate")
3.
............... (lowest authorization, read only, only levels "Info" and "Operate")