34
EN/11.2018/G67C © STULZ GmbH – all rights reserved
wib8000 original instructions
6. Operation
6.1 Bus view
Up to 20 parameters can be indi-
vidually set for each unit in the
menu Config/web interface.
Browser tabs (dependant on browser)
For the naming of browser tabs the WIB8000 provides texts depending on the chosen view according to the
following principle:
1. system name followed by unit name
2. system name followed by bus name
3. system name followed by zone name
Below you see three examples for the naming of tabs. The view of bus 1 is being displayed. The view of zone 1
and view of unit 1-10 are covered by the tab "WIB8000 Bus 1".
The start point when setting unit parameters via the WIB module is the bus view or if existant the zone view.
By the bus view the parameter which characterize the unit and give a quick overview of the unit state are dis-
played box-shaped, where each box represents a unit/controller/bus participant.
1. Unit name
2. Unit state
(online, offline, alarm)
3. Unit type
(DX, GE, CW, Chiller)
4. Return air temperature actual value (for unit type DX, GE, CW)
Flow water temperature
(for unit type Chiller)
5. Return air humidity actual value
(for unit type DX, GE, CW)
Return water temperature
(for unit type Chiller)
6. Operating state
(on/off)
If an alarm has occurred for a unit, the unit box is displayed alternately with a normal and a reddish back-
ground. Simultaneously the alarm icon in the menu line blinks.