In the category "zone averaging" you can determine, whether the A/C unit sensor data which is actually in
standby is taken into account for calculating the zone average value (setting "YES") or not (setting "NO",
default).
After having done the settings click the "Reboot" button to put the settings into effect. The WIB8000 can now
be connected to the internal network by means of the Ethernet connection.
You can choose among the following
temperatures:
For the humidity four settings
are available:
Overload start
An overload start for a unit, for which you adjust this, is carried out if the adjusted temperature is exceeded or if
the adjusted humidity is higher than the measured humidity. To determine the overload operation stop you can
set a hysteresis for the temperature and humidity each.
For both parameters you can specify which measured value shall trigger the overload start (the average zone
value or the measured unit value).
Start window
BMS stop 1: This setting does not allow switching on and off the unit by the Start- and Stop buttons.
BMS stop 2: With this setting switching off the unit by the Stop button has the effect that it is treated like a
valid alarm. A standby unit is then started within the zone.