non-ASCII characters, make sure that, enabling the trap unit name option "extended", all trap receivers, which
receive messages from the WIB8000, support UTF-8 encoded trap value fields. Otherwise, there will be dis-
play problems at the SNMP client.
Trap 1 - 6
The SNMP host of the WIB8000 can be reached at the SNMP standard port 161.
The complete OID of a unit data point is assembled as follows:
<prefix>.<OIDaccordingtolist>.<busnumber>.<globalunitaddress>.<modulenumber>
<prefix>:
1.3.6.1.4.1.29462.10.2 (iso.org.dod.internet.private.enterprises.stulz.stulzWIB.
wibUnits)
<OIDacc.tolist>: 1.1.1.1.1.1.1.1170
(example:unittemperature)
<busnumber>:
1or2
(WIB8000bus,bywhichtheunitisconnected)
<globaladdress>: 0to65535
(adjustedattheunit)
<modulenumber>: 1to6
(always"1"forC7000IOCs)
The OID of the unit temperature of a C7000 controller with the address 15 on bus 2 would be:
1.3.6.1.4.1.29462.10.2.1.1.1.1.1.1.1.1170.2.15.1
Up to six traps can be configured, for each of which the community, the receiver the output port and the ver-
sion must be adjusted. Concerning the version you can choose among three options:
- v1:
Trap messages are sent to this receiver in the SNMP format 1.
- v2c:
Trap messages are sent to this receiver in the SNMP format 2c.
- both (default):
The receiver gets each trap message in format 1 and in format 2c.
(two messages for one event in total.)
NOTICE
In case of problems with the connection see