The Split-Air unit is supplied pre-charged with the right quantity of refrigerant for 5 m distance*
between the evaporating and motor-condensing unit. 80% of the pre-filled refrigerant is in the motor-
condensing unit, the remaining 20% is in the evaporating unit.
After having connected the refrigerant circuit, an additional quantity of the same refrigerant must be
added according to table 2 below, if the distance is more than 5 m.
In this table d= distance* (measured in meter) - 5m
TABLE 2: Additional charge of R407c refrigerant for piping distance* beyond 5m (maximum 30m)
NOTE: values applying with condensation T = 50°C.
Model
Piping distance*
R407c additional
charge (g)
CST40
up to 10 m
30 x d
from 10 to 30 m
115 + 53 x d
CST50
up to 10 m
30 x d
from 10 to 30 m
115 + 53 x d
CST60
up to 10 m
53 x d
from 10 to 30 m
85 + 70 x d
CST80
up to 10 m
53 x d
from 10 to 30 m
235 + 100 x d