E/0204/39/44
P
1
2
3
Technical features:
Power supply:
1,5 (o,4) A; 250 Vac - 0,1 A; 24 Vac
Humidity:
0...50% rel. h., non condensing
Operating temperature:
-20/+85°C
Max. pressure:
50 mbar
Contacts:
Micro switch with contacts of AgCdO (on/off)
Housing:
Plastic
Protection:
IP54
Protection class:
I
Diaphragm:
Silicone
Pressure connection:
Ø 6 tube
Range :
0,4 - 2,0 mbar
Differential press. : 0,2 mbar + 15%
P1 :
Connection of the high pressure
P2 :
Connection of the low pressure
Adjustment:
Using a screwdriver, you can adjust the desired differen-
tial pressure, over which the filter control triggers, at the
central screw.
Contact 3-1 opens, when the differential pressure increases to the
adjusted value. Simultaneously contact 3-2 closes, the signal is
transmitted by this contact.
11.11 MECHANICAL HYGROSTAT (
only in units controlled by C1010)
It is included in the standard configuration of units controlled by the C1010 microprocessor and
measures the air humidity at the internal intake. If the humidity exceeds an adjustable limit value,
the hygrostat sends a signal to the C1010 controller for high humidity alarm and enabling
dehumidification. The limit value is adjustable from 0% to 90% rel. humidity.
11.12 DIRTY FILTER ALARM DEVICE RFS
(standard only in units controlled by C1010, optional for mechanically controlled units)
It provides a signal, via the display ; which indicates the need to service the air filter
Wiring :
Содержание Split-Air CST 40
Страница 2: ...E 0204 39 2...
Страница 14: ...E 0204 39 14 A B C B C A Dimensions Outside Unit CST 40 50 400 800 350 580 54 5...
Страница 15: ...E 0204 39 15 A B C B C A 54 5 Dimensions Outside Unit CST 60 80 450 950 400 640...
Страница 23: ...E 0204 39 23 Airflow Outside Unit CST Refrigerant connections Condenser fan Condenser Compressor...
Страница 69: ...E 0204 39 69 27 x 0 34 mm SIGNAL CABLE 3m SIGC3 SEQUENCING CABLE 2m SEQC2 RJ11 connector 4 conductors...