E/0204/39/40
ADJUSTING SET-POINT/ALARM SET POINT PROCEDURE
Proceed as follows:
Before entering menus the display appears as shown
on the left. Press “MENU” key to enter the menus.
The display appears as shown on the left. Using
(UP) and
(DOWN) keys you can move through the
various menus of C1010. When you arrive at USER
SETUP (blinking at the last line of the display), press
“SET” key.
Now you are inside the USER SETUP menu. Using
(UP) and
(DOWN) keys you can move through the
various parameters modifiable inside the USER SET-
UP menu. The procedure to modify all these
parameters is the same. As an example, in the following
you can find the procedure to modify the temperature
set-point during cooling. Go with the arrow keys to
TEMPERATURE SETPOINT COOLING.
• Press “SET” key.
The last line (current value) will start to blink.
• Using
(UP) and
(DOWN) keys you can change
the value of this parameter.
• Press “SET” key to store the new selected value.
The same procedure can be followed to modify all
parameters inside USER SETUP menu. Here below,
you can find the list of all parameters modifiable inside
this menu.