E/0204/39/36
32°C
29,5°C
2,5°C
7°C
12,5°C
2,5°C
15°C
25°C
34°C
31.5°C
2,5°C
9°C
10°C
2,5°C
12,5°C
25°C
compressor
Operating Diagrams - C1010
Free Cooling Conditions
Unit 1
heating element
compressor
heating element
Unit 2*
SET2 SET1
SET2
SET1
Conditioner 1 operates with setting at 25°C, between 32°C and 29.5°C.
Heating elements operate with setting at 15°C, between 12.5°C and 15°C.
Conditioner 2 (optional) operates with setting at 25°C, between 34°C and 31.5°C.
Heating elements 2 (optional) operate with setting at 12.5°C, between 10°C and 12.5°C.
* only with LAN connection of both units
Содержание Split-Air CST 40
Страница 2: ...E 0204 39 2...
Страница 14: ...E 0204 39 14 A B C B C A Dimensions Outside Unit CST 40 50 400 800 350 580 54 5...
Страница 15: ...E 0204 39 15 A B C B C A 54 5 Dimensions Outside Unit CST 60 80 450 950 400 640...
Страница 23: ...E 0204 39 23 Airflow Outside Unit CST Refrigerant connections Condenser fan Condenser Compressor...
Страница 69: ...E 0204 39 69 27 x 0 34 mm SIGNAL CABLE 3m SIGC3 SEQUENCING CABLE 2m SEQC2 RJ11 connector 4 conductors...