E/0204/39/38
Dehumidification control
The dehumidification control is differently carried out corresponding to the unit equipment (with/
without el. reheat). The following diagrams are valid only with the optional humidity sensor.
The dehumidification is controlled via the room humidity and the room temperature.
Dehumidification
Dehumidification without el. reheat
Here the dehumidification is obtained by reducing the fan speed and simultaneous compressor
operation. Reducing the air flow with constant heat rejection brings air down to the dew point.
Therefore, humidity in the air condenses and deposits on the evaporator surface. When the surface
temperature of the evaporator goes below a factory-set value, the fan speed increases again.
Dehumidification is disabled below a certain value of internal temperature. When the internal
temperature increases again after a certain hysteresis, the dehumidification is enabled again, if the
dehumidification request is still present.
Dehumidification
Dehum.
Set point
(40%)
Dehumidification Start
(10%)
Room humidity
Dehumidifcation
Stop (1%)
Start
value
(20°C)
Stop
value
(15°C)
Set point
cooling
(25°C)
Room temp.
Содержание Split-Air CST 40
Страница 2: ...E 0204 39 2...
Страница 14: ...E 0204 39 14 A B C B C A Dimensions Outside Unit CST 40 50 400 800 350 580 54 5...
Страница 15: ...E 0204 39 15 A B C B C A 54 5 Dimensions Outside Unit CST 60 80 450 950 400 640...
Страница 23: ...E 0204 39 23 Airflow Outside Unit CST Refrigerant connections Condenser fan Condenser Compressor...
Страница 69: ...E 0204 39 69 27 x 0 34 mm SIGNAL CABLE 3m SIGC3 SEQUENCING CABLE 2m SEQC2 RJ11 connector 4 conductors...