© Stiebel 11091_SOM_9s.mon
us.ind
d
| 96
SOM 9s
7
User code and short menu -
Adjustment values
The access to some adjustment values can be restricted via
a user code (customer). For safety reasons, the user code
should generally be set to the customer code before the
controller is handed to the customer!
1. Expert 0262 (Factory setting)
All menus and adjustment values are shown and all values
can be altered.
2. Customer 0000
The expert level is not shown, adjustment values can be
changed partly (see below)
Î
In order to restrict the access, enter 0000 in the menu
item CODe.
The display changes to the status level. If the adjustment
channel is selected afterwards, the short menu shown below
will be available. The short menu suits the selected system.
Î
In order to authorize the access, enter 0262 in the menu
item CODe.
Channel
Factory setting
Adjustment range
Description
TIME
12:00
00:00 ... 23:59
Time
DT O
12 °R
2.0 ... 90.0 °R
Switch-on temperature difference tank
DT F
8 °R
1.0 ... 89.0 °R
Switch-off temperature difference tank
DT S
20 °R
3.0 ... 90.0 °R
Set temperature difference tank
S MAX
140 °F
40 ... 200 °F
Tank maximum limitation
DT1O
12 °R
2.0 ... 90.0 °R
Switch-on temperature difference tank 1
DT1F
8 °R
1.0 ... 89.0 °R
Switch-off temperature difference tank 1
DT 1S
20 °R
3.0 ... 90.0 °R
Set temperature difference tank 1
S1MAX
140 °F
40 ... 200 °F
Tank maximum limitation tank 1
DT2O
12 °R
2.0 ... 90.0 °R
Switch-on temperature difference tank 2
DT2F
8 °R
1.0 ... 89.0 °R
Switch-off temperature difference tank 2
DT 2S
20 °R
3.0 ... 90.0 °R
Set temperature difference tank 2
S2MAX
140 °F
40 ... 200 °F
Tank maximum limitation tank 2
LST2
ON
ON / OFF
Loading tank 2 on
MAN1
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 1
MAN2
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 2
MAN3
Auto
Auto / ON / OFF / n LO / n HI Manual operation pump 3
MAN4
Auto
Auto / ON / OFF
Manual operation pump 4
CODE
0000
0000 / 0262
User code
Code