© Stiebel 11091_SOM_9s.mon
us.ind
d
| 48
SOM 9s
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
CMIN1
50 °F
Minimum collector temperature 1
80
OTCO1
OFF
Option evacuated tube collector function 1
81
TCST1
07:00
Evacuated tube collector starting time 1
81
TCEN1
19:00
Evacuated tube collector ending time 1
81
TCRU1
30 s
Evacuated tube collector runtime 1
81
TCIN1
30 min
Evacuated tube collector standstill interval 1
81
OCFR
OFF
Option collector frost protection
81
CFR O
40 °F
Antifreeze temperature collector on
82
CFR F
42 °F
Antifreeze temperature collector off
82
COL 2 >
Collector 2
CEM2
270 °F
Collector emergency temperature 2
80
OCCO2**
OFF
Option collector cooling 2
80
CMAX2
230 °F
Maximum collector temperature 2
80
OCMI2
OFF
Option collector minimum limitation 2
80
CMIN2
50 °F
Minimum collector temperature 2
80
OTCO2
OFF
Option evacuated tube collector function 2
81
TCST2
07:00
Evacuated tube collector starting time 2
81
TCEN2
19:00
Evacuated tube collector ending time 2
81
TCRU2
30 s
Evacuated tube collector runtime 2
81
TCIN2
30 min
Evacuated tube collector standstill interval 2
81
LLOGI >
Loading logic
OOVRU*
OFF
Overrun option
84
COOL >
Cooling functions
OSYC**
OFF
System cooling
85
OSTC
OFF
Tank cooling
85
OHDP**
OFF
Heat dump
85
AH >
Backup heating option
AH O
110 °F
Backup heating switch-on temperature
87
AH F
120 °F
Backup heating switch-off temperature
87
t1O
06:00
Switch-on time 1
88
t1F
22:00
Switch-off time 1
88
t2O
00:00
Switch-on time 2
88
t2F
00:00
Switch-off time 2
88
t3O
00:00
Switch-on time 3
88
t3F
00:00
Switch-off time 3
88
PUMP >
Pump speed
PUMP1
OnOF
Speed variant pump 1
79
PUMP2
OnOF
Speed variant pump 2
79
PUMP3
OnOF
Speed variant pump 3
79
MAN >
Manual mode
MAN1
Auto
Manual mode 1
88
MAN2
Auto
Manual mode 2
88
MAN3
Auto
Manual mode 3
88
MAN4
Auto
Manual mode 4
88
BLPR >
OFF
Blocking protection
88
OTDIS >
OFF
Thermal disinfection option
89
OPARR >
OFF
Parallel relay option
90
OHQM >
OFF
Energy metering option
90
GFDS >
OFF
Registration Grundfos sensors
90
PRS* >
OFF
Pressure monitoring option
92
DATE>
Enter date
92
LANG >
En
Language
93
UNIT >
°F
Unit
92
OSDC >
SD card option
93
CODE
0000
User code
96
RESET
OFF
Factory setting
* This channel is only available if the Grundfos sensors have been registered in the gFDS channel.
** are blocked against each other