Adjustment channels
Channel
Sub channel 1
Sub channel 2
Factory
setting
Change to
Description
Page
CMAX
230 °F
Maximum collector temperature
80
OCMI
OFF
Option collector minimum limitation
80
CMIN
50 °F
Minimum collector temperature
80
OTCO
OFF
Option evacuated tube collector function
81
TCST
07:00
Evacuated tube collector starting time
81
TCEN
19:00
Evacuated tube collector ending time
81
TCRU
30 s
Evacuated tube collector runtime
81
TCIN
30 min
Evacuated tube collector standstill interval
81
OCFR
OFF
Option collector frost protection
82
CFR O
40 °F
Antifreeze temperature collector on
82
CFR F
42 °F
Antifreeze temperature collector off
82
LLOGI >
Loading logic
ODB >
OFF
Drainback option
84
OOVRU*
OFF
Overrun option
84
COOL >
Cooling functions
OSYC**
OFF
System cooling
85
OSTC
OFF
Tank cooling
85
OHDP**
OFF
Heat dump
85
AH >
Backup heating option
AH O
110 °F
Backup heating switch-on temperature
87
AH F
120 °F
Backup heating switch-off temperature
87
t1O
06:00
Switch-on time 1
88
t1F
22:00
Switch-off time 1
88
t2O
00:00
Switch-on time 2
88
t2F
00:00
Switch-off time 2
88
t3O
00:00
Switch-on time 3
88
t3F
00:00
Switch-off time 3
88
PUMP >
Pump speed
PUMP1
OnOF
Speed variant pump 1
79
PUMP2
OnOF
Speed variant pump 2
79
PUMP3
OnOF
Speed variant pump 3
79
MAN >
Manual mode
MAN1
Auto
Manual mode 1
88
MAN2
Auto
Manual mode 2
88
MAN3
Auto
Manual mode 3
88
MAN4
Auto
Manual mode 4
88
BLPR
>
OFF
Blocking protection
88
OTDIS >
OFF
Thermal disinfection option
89
OPARR >
OFF
Parallel relay option
90
OHQM >
OFF
Energy metering option
90
GFDS >
OFF
Registration Grundfos sensors
90
PRS* >
OFF
Pressure monitoring option
92
DATE>
Enter date
92
LANG >
En
Language
93
UNIT >
°F
Unit
92
OSDC >
SD card option
93
CODE
0000
User code
96
RESET
OFF
Factory setting
* This channel is only available if the Grundfos sensors have been registered in the gFDS channel.