© Stiebel 11091_SOM_9s.mon
us.ind
d
45 |
SOM 9s
The controller compares the temperatures at the coll-
ector sensors S1 and S5 to the tank temperature at
sensor S2. If one of the measured temperature diffe-
rences is higher than the adjusted switch-on tempera-
ture differences, the corresponding pump (R1, R2) or
both pumps will be activated and the tank will be loaded.
Heat transfer control to an existent tank (R3) can be carried
out with another temperature differential function (S3-heat
source/S4-heat sink).
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
18
System
78
LOAD >
Loading
DT O
12 °R
Switch-on temperature difference
78
DT F
8 °R
Switch-off temperature difference
78
DT S
20 °R
Set temperature difference
78
RIS
4 °R
Rise
78
S MAX
140 °F
Tank maximum limitation
78
SMAXS
2
Sensor tank max
79
COL 1 >
Collector 1
CEM1
270 °F
Collector emergency temperature 1
80
OCCO1**
OFF
Option collector cooling 1
80
CMAX1
230 °F
Maximum collector temperature 1
80
OCMI1
OFF
Option collector minimum limitation 1
80
Sensor/Ter-
minal
Designation
Description
S1
TCOL1
Temperature collector 1
S2
TST1B
Temperature tank 1 bottom
S3
TSTT
Temperature tank 1 top
S4
TST2B
Temperature tank 2 bottom
S5
TCOL2
Temperature collector 2
VFS
Optional sensor for measurement
purposes or options
RPS
V40
Relay
Description
R1
Solar pump collector 1
R2
Solar pump collector 2
R3
Heat exchange pump
R4
optional:
Thermal disinfection
Parallel relay
Heat dump
System 18
Solar system with east-/west collectors and heat exchange control
R3
R2
R1
S5
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in