S Series FW 3.02.02
www.stenner.com
40
No
Returns display to the
Pulse
menu without enabling the
signal overrun alarm.
PULSE
page 1 of 2
Allows user to configure the pump to run for a specified period of time when it receives a specified
number of signals from a dry contact or an open collector input.
To program the pump for
Pulse
control mode, set the activation parameters in
Program Settings
, return to the
Pulse
Control
menu and program the desired options under
Alarm Settings
, then exit to the
Main Menu
via the
Go To Main
Menu
option.
The minimum allowable run time is 20.0 seconds.
A signal overrun occurs when the pump receives sufficient pulses to activate another run cycle while
the pump is already in a run cycle. This means that the process flow is greater than what the program settings allow for.
The pump will ignore an activation while it is in a run cycle. A signal overrun condition will lead to incorrect dosing.
CONTROL MODES MENU
continued
Pulse
- Program Settings
- Alarm Settings
- Go to Main Menu
Pulse
- Program Settings
- Alarm Settings
- Go to Main Menu
To
Main Menu
Select “Yes” to shut off the pump in the
event of a signal overrun alarm. Select
“No” to allow the pump to continue to run
in the event of a signal overrun alarm.
Pulse
- Program Settings
- Alarm Settings
- Go to Main Menu
Alarm on Overrun?
Yes
yes/no
set
Yes
Stop Pump on H ALM?
Yes
yes/no
set
To
Pulse
menu
Continued on next page
Control Mode
- 4-20mA
- 0-10VDC
- Pulse
Sets a value in a menu
NAVIGATION
Moves one step back in
a menu, when permitted
Moves up in a menu, toggles
between options, or increase a value
Moves down in a menu, toggles
between options, or decreases a value
Holding the or button causes the numbers to change rapidly.