CONTROL MODES MENU
continued
0-10VDC
page 2 of 3
To program the pump for 0-10VDC control mode, set the response curve in
Program Settings
, return
to the
0-10VDC Control
menu and program the desired options under
Alarm Settings
, then exit to
the
Main Menu
via the
Go To Main Menu
option.
Control Mode
- Manual
- 4-20mA
- 0-10VDC
0-10 VDC
- Program Settings
- Alarm Settings
- Go to Main Menu
0-10 VDC
- Program Settings
- Alarm Settings
- Go to Main Menu
0-10 VDC
- Program Settings
- Alarm Settings
- Go to Main Menu
To
Main Menu
Minimum Signal
_ 0.0 VDC
adjust
set
To
0-10 VDC
menu
Speed at Min VDC
_ _ 0%
Maximum Signal
10.0 VDC
Speed at Max VDC
100 %
When ENTER is pressed for the final
digit, the display will return to the
0-10VDC
menu.
adjust
set
adjust
set
adjust
set
Set the response curve by entering the
Minimum Signal
, the % pump speed at
Minimum Signal
, and the % pump
speed at
Maximum Signal
.
Sets a value in a menu
NAVIGATION
Moves one step back in
a menu, when permitted
Moves up in a menu, toggles
between options, or increase a value
Moves down in a menu, toggles
between options, or decreases a value
Holding the or button causes the numbers to change rapidly.