6

 

2.3 Menu 

"READINGS"

 

By pushing the OK button within the menu

 "READINGS"

  you can fetch the various temperatures of the sensors 

installed. Moreover, the controller stores minimum and maximum temperature values of the collector, storage tank 
top and storage tank bottom. These values can be reset just as the solar circulation pump‘s operating hours over a 
certain period of time or the measured heat quantity (using the function calorimetry). Please note that only the delta 
values at the second job will be deleted. (d hours; greek delta = difference). The total value (greek 

= total value) 

cannot be lost and will be summed up over the complete lifetime of the controller. Resetting the difference value „d“ 
can be achieved by pushing the OK button for 2 sec.  

 
2.4 Menu 

"ADJUSTMENTS"

 

The submenu of the configurated values are protected against unauthorized or unintentional use. If you intend to 
change them, press OK 

and

 MENU for 2 sec 

at the same time

. Submenus like parameters, functions or manual 

operation can be selected via the OK button. By pushing the MENU button you get back to a higher menu. 
 
Changing the 

“PARAMETERS”

 values: 

1.  select parameter with button 

 

2.  press OK for 2 sec 
3.  change the value with button 

 

4.  leave parameter menu by pressing OK for 2 sec 
 
Changing the “

FUNCTIONS”

 configuration: 

1.  select function with button 

 

2.  press OK for 2 sec 
 

“MANUAL OPERATION”

 manual switch of output R1 

1.  select output R1 or R2 with button 

 

2.  press OK for 2 sec 
 
Initialization of all parameters and functions to the preset manufactured status: 
1. select 

menu 

"initialisation preset configuration"

 

2.  press OK for 2 sec 
 

Attention! 

Readings and parameters will only be displayed when the corresponding function has actually been selected 
within the menu 

"FUNCTIONS"

Example: Selecting the function calorimetry 
It is only now that the temperatures T4, T5 and the measured calorimetry appears in the menu READINGS. Moreover, 
within the menu Parameter you may change the volume flow dispenser´s pulse valency configuration and the 
proportion of mixture of the heat transfer medium. 
In the appendix you will find diagrams that give an overview on potential additional configuration parameters and/or 
reading indications after selecting an additional controller function. 

Note:  

All functions are listed in detail in paragraph 3 of these operating instructions. In order to exclude operation 

faults you should be sure to have understood the connection and the usage of the corresponding function 

BEFORE changing it.

 

 
 

System controller for thermal solar systems with monitoring functions 

 

3.1 

Overall function of the system controller in the solar system

 

The controller is a temperature difference controller driven by microprocessors and is used for monitoring and 
controlling thermal solar systems and, if wanted, am accessory heating system or circulation pump. 
The microprocessor takes all important readings, calculates the control function and controls the servo components of 
the system. Beside controlling the system the controller also undertakes important monitoring and safety functions.  
The controller has 5 analog inputs for measuring the temperature, a digital impuls input point and 2 outputs for 
triggering circulation pumps. For this purpose we have integrated a timer with 3 possible times. 
The controller can be used in connection with various system concepts. A collector temp. sensor (T1), a storage temp. 
sensor (T2) in the bottom storage area for the limitation of the max. stored temperature and a storage sensor in the 
top storage area (T3) for additional temperature indication or for triggering a heat system pump, are standard system 
components. For triggering a circulation pump you can - in additon to the adjustable time intervals - also utilize the 
temperature sensor (paragraph 3.2.7). 

Содержание Suntana

Страница 1: ...Instructions for installation and operation System controller for thermal solar systems Suntana 700 676 SOLARTHERMIE SOLAR THERMAL SOLAR T RMICO SOLAIRE THERMIQUE SOLARE TERMICO EN...

Страница 2: ...onfiguration 11 5 Installation and operation 12 6 Malfunction and sources of error 14 7 Legal Guarantee 16 8 Technical data 17 9 Preset standard configuration 17 10 Appendix 19 Ecological Chlorine fre...

Страница 3: ...ter or buffer store For the installation of the other components such as the solar collectors pump group and the storage basins please follow the corresponding installation instructions of the manufac...

Страница 4: ...l parameters and functions to the original preset configuration you can do so in the menu initialisation preset configuration paragraph 2 4 and 5 In these operating instructions menus that are only ac...

Страница 5: ...5 illustration 2 Diagram of different menu 2 2 Example illustration on menu driven operation With this example you can see how to fetch current and stored readings within the main menu READINGS...

Страница 6: ...is only now that the temperatures T4 T5 and the measured calorimetry appears in the menu READINGS Moreover within the menu Parameter you may change the volume flow dispenser s pulse valency configura...

Страница 7: ...ff temperature difference Example The parameter value of the switch on temperature difference is 8 Celvin the parameter value of the switch off temp is 4 Celvin On the point of measurement at the bott...

Страница 8: ...ises After exceeding the preset temperature with the description collector temp limitation menu parameter to be measured at the collector temp sensor T1 the solar circulation pump is again switched on...

Страница 9: ...mp can be triggered temperature linked by an additional temperature sensor at T4 or time linked by certain time windows Both functions may be combined at any time The combination of the following circ...

Страница 10: ...OPERATION press OK for 2 sec to achieve another switch status This status remains until the submenu manual operation is left by pushing the menu button Attention Only after leaving the submenu manual...

Страница 11: ...s can be used and are automatically recognized by the controller Note This function is not valid for the collector sensor since the PT1000 and KTY value of resistance partly overlap and so a faultless...

Страница 12: ...roller are only to be conducted by specialists The controller is protected against overload and short circuit 5 1 Location of installation The controller is designed for installation on vertical walls...

Страница 13: ...sleeves for strands Outsid the controller the wires must be strain relieved Storing and collector sensor are to be connected e to the prescribed draws illustration 6 Pos to In this context the polari...

Страница 14: ...radio sets microwaves etc conductors that carry reading signals have to be screened The sensor cable can be extended to approx 100 m For this purpose please use a profile section of the extension cab...

Страница 15: ...hat mig installed air within the solar circuit Usage of another solar liquid than Tyfocor Indication of error in the LCD display Short circuits and interruptions of each single temp sensor are only in...

Страница 16: ...ance with German statutory regulations there is a 2 year legal guarantee on this product for the customer ring and material faults that occur in the product during the legal guarantee t ll aims are to...

Страница 17: ...alternative KTY81 210 with 2 0 m PVC cable colour grey measurin 1 5 m silicon cable colour red brown Preset standard configurations te a initialisation preset config preset configuration by the nufac...

Страница 18: ...cooling 3 K below STL constant storage tank cooling hysteresis 3 K constant restore prevention 130 C constant restore prevention hysteresis 4 K constant heating system ON temperature HSONT 20 C HSOFF...

Страница 19: ...r ntrol temperature linked circulation co OFF time linked circulat contr ation control time linked circul OFF T1 KTY T1 KTY OFF PT1000 OFF speed control speed control ON 10 Appendix Diagrams on menu c...

Страница 20: ...illustration D ADJUSTMENTS READINGS OK OK Menu PARAMETERS OK Menu FUNCTIONS OK Menu storage temp limitation C collector temp limitation 110 C collector temp limitation ON calorimetry OFF OK OK OK Menu...

Страница 21: ...C heating system ON OK Menu heating system OFF 52 C calorimetry OFF OK FUNCTIONS OK Menu OK time 12 00 indexing time1 06 00 to 09 00 indexing time2 12 00 to 14 00 indexing time3 18 00 to 21 00 OK Men...

Страница 22: ...contr OK Menu MAN OPERATION 2 Time linked circulation control illustration H ADJUSTMENTS READINGS OK PARAMETERS OK Menu storage temp limitation C time 12 00 time linked OFF circulat contr OK Menu FUNC...

Страница 23: ...ATION calorimetry illustration J ADJUSTMENTS READINGS OK col C stb C T4 C T5 C calorimetry kWh 00000 d 00000 PARAMETERS OK Menu storage temp limitation C calorimetry 1 liter puls OK OK Menu calorimetr...

Страница 24: ...ON manual operation output R1 solar loop pump solar loop pump OFF OK Menu OPERATION MAN OK solar loop pump OFF output R2 OFF MAN OK Menu OPERATION OK OK Menu MAN OPERATION solar loop pump OFF Initiali...

Страница 25: ...700676...

Отзывы: