17
8 Technical
Data
•
Nominal voltage
230 Volt (
±
15 %), 50 Hz
[optional 115 Volt (±15 %), 60 Hz]
•
Max. self consumption
≤
1,0 W
•
6 inputs
5 x temperature determination
1 x pulse determination
PT1000 or KTY81-210
pulse counter 1 ... 99
liter/pulse
•
2 outputs
R1
R as switch
2
output 230 V [115 V]
or R2 voltage-free
Triac for speed control, max. switch. capacity 200 W at 230 V [or 100W at 115V]
relay, max. switching capacity 800 W at 230 V [or 400W at 115 V]
remove wire strap (drive, e.g. gas burners)
•
All outputs are protected against overload and short circuit
•
Adjustment ranges
Turn-on temperature difference
Turn-off temperature difference
4...17 K
2...15 K
•
Automatic timer
24 hours, 3 response times freely programmable
•
Display
LCD display, 2 lines with 16 char each, menu-driven clear text display
•
Protection
IP 20 / DIN 40050
•
Permissible ambient temperature
0 °C ... +45 °C
•
Installation
wall installation
•
Weight
490 g
•
Casing
Recycleable 3-part plastic casing
•
Dimensions l x w x h (mm)
150 x 215 x 43 mm
Temperature sensors
•
storage tank
(*)
: PT1000
•
collector : PT1000
(**)
1,5 m silicon cable (colour black), measuring range up to 180° C
1,5 m silicon cable (colour black), measuring range up to 180° C
(*)
alternative: KTY81-210 with 2,0 m PVC-cable (colour grey), measurin
1,5 m silicon-cable (colour red-brown),
Preset standard configurations
te a
"initialisation preset config."
(preset configuration by the
nufac
n of paramenter values and function are deleted from the
thin the thermostat function heat
g range up to 105 °C
(**)
alternative: KTY81-210 with
measuring range up to 150 °C
9
In the submenu
"MAN.OPERATION"
you can configura
ma
turer). This means that individual configuratio
controller memory and that subsequently the preset configurations are valid.
After a power failure there is no need to put in parameter values or function configurations since these values are
stored in the EEProm of the controller. If the automatic time switch is used wi
coasting or circulation please adjust the time. For this purpose the menu window TIME automatically appears after a
potential power failure.
On delivery the following parameters and functions are configurated. Any changes done to the parameter values or
functions should be noted in the following chart in order to be able to find and eliminate the source of error in the
case of failure or a erroneous misadjustment. Furthermore, we would ask you to enclose a sketch of your hydraulic
system together with the complete chart in the case of any reclamation you pass on to your dealer or manufacturer.