9

3.2.6  Thermostat function heating system (

"heating system"

) (Appendix 10, illustration F) 

 

The thermostat function heating system allows for warming up a warm water service 
tank by a heating tank. If an adjustable temp. (menu parameter: 

"heating system ON"

on sensor T3 falls below 3 adjustable time windows (menu parameter

: "indexing time 

1: ... "

) the circulation pump P2 at output R2 is activated. The circulation pump 

remains in operation as long as an adjustable switch-off temp. is reached (menu 
parameter: 

"heating system OFF"

 or as long as the time window in question is 

exceeded. 
Preset configurations are 

"heating system ON:45°C"

 and 

"heating system OFF: 52°C"

For safety reasons ON and OFF values are interlocked. Both values can be adjusted 
against each other up to a maximum difference of 3 Celvin . 
The indexing times of the integrated automatic time switch are preset to "indexing 

time 1: 06.00 to 09.00 h", "indexing time 2: 12:00 to 14:00 h" and "indexing time 3: 18:00 to 21:00 h". Winter and 
summer daylight saving time are not preset configurations and must be adjusted manually, if needed. 
Indexing times can be changed as follows:  
Select indexing time be pushing the buttons 

. Press one of them for 2 sec and change the time by pressing 

Finally press OK for 2 sec to store this configuration. 
If you cannot select the desired thermostat function another one is already activated.  
For safety reasons the thermostat functions storage cooling, heat coasting and circulation have been interlocked on 
software basis. So please switch off one thermostat function first and then switch on another one.  

Note: 

Please note that a circulation pump can be triggered with either 230 V [optional 115 V] (e. g. old heating tanks) 
directly (preset terminal board must be installed) or indirectly via a separate tank control (e. g. gas condensing boiler) 
or the power-free output R2 (preset terminal board must be removed, or else tank control may be destroyed). 

Note: 

The controller offers the thermostat function storage cooling. Please follow the relevant VDE norms for the proper use 
of the system. 

 

3.2.7  Thermostat functions circulation control 

 

The controller offers the possibility to trigger a circulation pump via output R2. 
This pump can be triggered temperature-linked by an additional temperature 
sensor at T4 or time-linked by certain time windows. Both functions may be 
combined at any time. The combination of the following circulation functions 
allows for reducing circulation to a minimum. This saves energy for operating the 
pump, reduces circulation losses in the pipelines and improves warmth bedding in 
the service water tank. Circulation losses in detached houes may easily amount to 
10 to 30 % of the energy that is need for warm water supply.  
If you cannot select the desired thermostat function another one is already 
activated. For safety reasons the thermostat functions storage cooling, heat 
coasting and circulation have been interlocked on software basis. So please switch 
off one thermostat function first and then switch on another one.  
 

A) temperature-linked circulation control 

(

"temp.-linked circulat. contr."

(Appendix 10, illustration G): 

This function needs an additional temperature sensor T4 at the return of the circulation pipeline. After falling below 
the adjustable value (menu parameter: 

"circulation ON"

) the circulation pump switches on and remains in operation 

until the switch-off value - also adjustable - (menu parameter: 

"circulation OFF"

) is reached. In order to avoid wrong 

measurements due to heat transfer of the pipeline you should provide for a minimum of 1.50m to the storage basin 
when you install the sensor. 

Note:

 If you intend to use a calorimeter in addition to this function (paragraph 3.3.2) you can only use it "with 

restrictions". As in this case the sensor T4 is used as circulation sensor the controller automatically registers the heat 
quantity from temperatures T1 and T4 and the external volume flow measuring device´s discharge. 

B) Time-linked circulation control 

(

"time-linked circulat. contr."

)

 (Appendix 10, illustration H) 

Without an additional temp. sensor a circulation pump may be operated via three different time windows. During the 
adjusted time window the pump will be in operation for the corresponding period of time. First of all you have to 
chose a time within the menu parameter. By selecting one of the indexing times 1 to 3 certain circulation cycles may 
be selected manually.  
Indexing times can be changed as follows:  
Select indexing time be pushing the buttons 

. Press one of them for 2 sec and change the time by pressing 

Finally press OK for 2 sec to store this configuration. 

Содержание Suntana

Страница 1: ...Instructions for installation and operation System controller for thermal solar systems Suntana 700 676 SOLARTHERMIE SOLAR THERMAL SOLAR T RMICO SOLAIRE THERMIQUE SOLARE TERMICO EN...

Страница 2: ...onfiguration 11 5 Installation and operation 12 6 Malfunction and sources of error 14 7 Legal Guarantee 16 8 Technical data 17 9 Preset standard configuration 17 10 Appendix 19 Ecological Chlorine fre...

Страница 3: ...ter or buffer store For the installation of the other components such as the solar collectors pump group and the storage basins please follow the corresponding installation instructions of the manufac...

Страница 4: ...l parameters and functions to the original preset configuration you can do so in the menu initialisation preset configuration paragraph 2 4 and 5 In these operating instructions menus that are only ac...

Страница 5: ...5 illustration 2 Diagram of different menu 2 2 Example illustration on menu driven operation With this example you can see how to fetch current and stored readings within the main menu READINGS...

Страница 6: ...is only now that the temperatures T4 T5 and the measured calorimetry appears in the menu READINGS Moreover within the menu Parameter you may change the volume flow dispenser s pulse valency configura...

Страница 7: ...ff temperature difference Example The parameter value of the switch on temperature difference is 8 Celvin the parameter value of the switch off temp is 4 Celvin On the point of measurement at the bott...

Страница 8: ...ises After exceeding the preset temperature with the description collector temp limitation menu parameter to be measured at the collector temp sensor T1 the solar circulation pump is again switched on...

Страница 9: ...mp can be triggered temperature linked by an additional temperature sensor at T4 or time linked by certain time windows Both functions may be combined at any time The combination of the following circ...

Страница 10: ...OPERATION press OK for 2 sec to achieve another switch status This status remains until the submenu manual operation is left by pushing the menu button Attention Only after leaving the submenu manual...

Страница 11: ...s can be used and are automatically recognized by the controller Note This function is not valid for the collector sensor since the PT1000 and KTY value of resistance partly overlap and so a faultless...

Страница 12: ...roller are only to be conducted by specialists The controller is protected against overload and short circuit 5 1 Location of installation The controller is designed for installation on vertical walls...

Страница 13: ...sleeves for strands Outsid the controller the wires must be strain relieved Storing and collector sensor are to be connected e to the prescribed draws illustration 6 Pos to In this context the polari...

Страница 14: ...radio sets microwaves etc conductors that carry reading signals have to be screened The sensor cable can be extended to approx 100 m For this purpose please use a profile section of the extension cab...

Страница 15: ...hat mig installed air within the solar circuit Usage of another solar liquid than Tyfocor Indication of error in the LCD display Short circuits and interruptions of each single temp sensor are only in...

Страница 16: ...ance with German statutory regulations there is a 2 year legal guarantee on this product for the customer ring and material faults that occur in the product during the legal guarantee t ll aims are to...

Страница 17: ...alternative KTY81 210 with 2 0 m PVC cable colour grey measurin 1 5 m silicon cable colour red brown Preset standard configurations te a initialisation preset config preset configuration by the nufac...

Страница 18: ...cooling 3 K below STL constant storage tank cooling hysteresis 3 K constant restore prevention 130 C constant restore prevention hysteresis 4 K constant heating system ON temperature HSONT 20 C HSOFF...

Страница 19: ...r ntrol temperature linked circulation co OFF time linked circulat contr ation control time linked circul OFF T1 KTY T1 KTY OFF PT1000 OFF speed control speed control ON 10 Appendix Diagrams on menu c...

Страница 20: ...illustration D ADJUSTMENTS READINGS OK OK Menu PARAMETERS OK Menu FUNCTIONS OK Menu storage temp limitation C collector temp limitation 110 C collector temp limitation ON calorimetry OFF OK OK OK Menu...

Страница 21: ...C heating system ON OK Menu heating system OFF 52 C calorimetry OFF OK FUNCTIONS OK Menu OK time 12 00 indexing time1 06 00 to 09 00 indexing time2 12 00 to 14 00 indexing time3 18 00 to 21 00 OK Men...

Страница 22: ...contr OK Menu MAN OPERATION 2 Time linked circulation control illustration H ADJUSTMENTS READINGS OK PARAMETERS OK Menu storage temp limitation C time 12 00 time linked OFF circulat contr OK Menu FUNC...

Страница 23: ...ATION calorimetry illustration J ADJUSTMENTS READINGS OK col C stb C T4 C T5 C calorimetry kWh 00000 d 00000 PARAMETERS OK Menu storage temp limitation C calorimetry 1 liter puls OK OK Menu calorimetr...

Страница 24: ...ON manual operation output R1 solar loop pump solar loop pump OFF OK Menu OPERATION MAN OK solar loop pump OFF output R2 OFF MAN OK Menu OPERATION OK OK Menu MAN OPERATION solar loop pump OFF Initiali...