Apart from this the controller allows for registrating the calorimetry fed into the service water storage basin by an 
additional volume flow dispenser and the temperatures in the solar forward and backward movement. The volume 
flow dispenser is a traditional water meter with pulse output point. It is important that the volume flow dispenser 
resists the higher temperatures within the solar circuit. This is the reason why you should not use cold water but warm 
or hot water meters sold by authorized dealers. 

 

3.2 Regulation 

function

 

Function overview 

Š

 "ON" and "OFF function" of the temp. difference regulation  

   (menu 

"On-temperature difference"

 = ON-Tdiff; menu 

"Off-temperature difference"

 = OFF-TDiff) 

Š

 menu 

"speed control" 

of the solar circulation pump 

Š

 

"storage tank temperature limitation"

 (menu 

"storage temp. limitation"

Š

 

"collector temperature limitation"

 (menu 

"collector temp. limitation"

Š

 Thermostat functions 

(due to software lock only one function to be selected)

 

 

y

 menu 

"storage tank cooling"

 

 

y

 

temperature

 

and time-linked

 

"heating system" 

(menu 

"heating system"

 

y

 

temperature

 

and time-linked "circulation control"

 (menu 

"temp.-linked circulat. contr."

, menu 

"time-linked  

 

  circulat. contr."

Š

 menu 

"antifreezing protection"

 

 

Š

 

"Manual operation"

 of the switch outputs (menu 

"MAN.OPERATION" 

 

3.2.1 

"On-temperature difference"

 and 

"Off-temperature difference"

 function of the temperature 

difference regulation (Appendix 10, illustration A) 

 

The solar circulation pump P1 is switched on by a temp. difference function. As soon 
as the collector temp T1 is a certain temperature difference (to be adjusted within 
the menu parameter "On-temperature difference"

 

higher than the sensor`s "storage 

tank bottom" T2 temp. the circulation pump will be switched on. 
In order to avoid a permanent ON and OFF of the solar circulation pump it only 
switches off automatically after falling below an adjusted temperature difference (to 
be configurated within the menu parameter "Off-temperature difference"). 
Example: 
The parameter value of the switch-on temperature difference is 8 Celvin, the 
parameter value of the switch-off temp. is 4 Celvin. On the point of measurement at 
the bottom of the storage tank (T2) 20°C are registered, i. e. in this case the solar 
circulation pump will be switched on at a collector temp. of 28°C and will be 
switched off at a collector temp of 24°C.  
 

IMPORTANT: 

The preset values of the switch-on (8 Celvin) and switch-off (4 Celvin) temperature difference have been proven 
standard configuration for years. Changing these values is thus only necessary in exceptionate situations, e. g. long 
pipeline distances. Switch-on and switch-off temperature differences are interlocked. Both values can be adjusted to a 
maximum of 2 Celvin against each other so that misconfiguration are avoided. 

 
 

3.2.2 

"speed control"

 of the solar circulation pump (Appendix 10, Illustration B) 

The controller has an electronic relay for the regulation of a circulation pump´s speed (P1) within the solar circuit. By 
regulation this speed the temperature difference between collector and storage tank is to be kept on a constant level. 
When using solar circulation pumps with changeable cycle speed stages the highest stage (in most cases stage 3) 
should be adjusted. This adjustment is done directly by moving the pump speed switch. The speed regulation 
automatically adjusts the necessary performance.  
The regulating performance of the speed control corresponds to a "PI" controller (proportional integral controller). The 
"P" part serves for a fast stabilisation of the regulation process and "I" part serves for a fast achievement of the preset 
set point. This controller is – due to its precise adjustment – extraordinarily rugged and it is not necessary for the user 
to conduct any detailed configuration. 
Nevertheless, you have the possibility to switch off the speed control within the menu functions “speed control”. Then 
the controller works just as a traditional temp. difference controller and takes care that the circulation pump delivers a 
constant volume flow (if the switch-on conditions are fulfilled). 
 
 
 
 

Содержание Suntana

Страница 1: ...Instructions for installation and operation System controller for thermal solar systems Suntana 700 676 SOLARTHERMIE SOLAR THERMAL SOLAR T RMICO SOLAIRE THERMIQUE SOLARE TERMICO EN...

Страница 2: ...onfiguration 11 5 Installation and operation 12 6 Malfunction and sources of error 14 7 Legal Guarantee 16 8 Technical data 17 9 Preset standard configuration 17 10 Appendix 19 Ecological Chlorine fre...

Страница 3: ...ter or buffer store For the installation of the other components such as the solar collectors pump group and the storage basins please follow the corresponding installation instructions of the manufac...

Страница 4: ...l parameters and functions to the original preset configuration you can do so in the menu initialisation preset configuration paragraph 2 4 and 5 In these operating instructions menus that are only ac...

Страница 5: ...5 illustration 2 Diagram of different menu 2 2 Example illustration on menu driven operation With this example you can see how to fetch current and stored readings within the main menu READINGS...

Страница 6: ...is only now that the temperatures T4 T5 and the measured calorimetry appears in the menu READINGS Moreover within the menu Parameter you may change the volume flow dispenser s pulse valency configura...

Страница 7: ...ff temperature difference Example The parameter value of the switch on temperature difference is 8 Celvin the parameter value of the switch off temp is 4 Celvin On the point of measurement at the bott...

Страница 8: ...ises After exceeding the preset temperature with the description collector temp limitation menu parameter to be measured at the collector temp sensor T1 the solar circulation pump is again switched on...

Страница 9: ...mp can be triggered temperature linked by an additional temperature sensor at T4 or time linked by certain time windows Both functions may be combined at any time The combination of the following circ...

Страница 10: ...OPERATION press OK for 2 sec to achieve another switch status This status remains until the submenu manual operation is left by pushing the menu button Attention Only after leaving the submenu manual...

Страница 11: ...s can be used and are automatically recognized by the controller Note This function is not valid for the collector sensor since the PT1000 and KTY value of resistance partly overlap and so a faultless...

Страница 12: ...roller are only to be conducted by specialists The controller is protected against overload and short circuit 5 1 Location of installation The controller is designed for installation on vertical walls...

Страница 13: ...sleeves for strands Outsid the controller the wires must be strain relieved Storing and collector sensor are to be connected e to the prescribed draws illustration 6 Pos to In this context the polari...

Страница 14: ...radio sets microwaves etc conductors that carry reading signals have to be screened The sensor cable can be extended to approx 100 m For this purpose please use a profile section of the extension cab...

Страница 15: ...hat mig installed air within the solar circuit Usage of another solar liquid than Tyfocor Indication of error in the LCD display Short circuits and interruptions of each single temp sensor are only in...

Страница 16: ...ance with German statutory regulations there is a 2 year legal guarantee on this product for the customer ring and material faults that occur in the product during the legal guarantee t ll aims are to...

Страница 17: ...alternative KTY81 210 with 2 0 m PVC cable colour grey measurin 1 5 m silicon cable colour red brown Preset standard configurations te a initialisation preset config preset configuration by the nufac...

Страница 18: ...cooling 3 K below STL constant storage tank cooling hysteresis 3 K constant restore prevention 130 C constant restore prevention hysteresis 4 K constant heating system ON temperature HSONT 20 C HSOFF...

Страница 19: ...r ntrol temperature linked circulation co OFF time linked circulat contr ation control time linked circul OFF T1 KTY T1 KTY OFF PT1000 OFF speed control speed control ON 10 Appendix Diagrams on menu c...

Страница 20: ...illustration D ADJUSTMENTS READINGS OK OK Menu PARAMETERS OK Menu FUNCTIONS OK Menu storage temp limitation C collector temp limitation 110 C collector temp limitation ON calorimetry OFF OK OK OK Menu...

Страница 21: ...C heating system ON OK Menu heating system OFF 52 C calorimetry OFF OK FUNCTIONS OK Menu OK time 12 00 indexing time1 06 00 to 09 00 indexing time2 12 00 to 14 00 indexing time3 18 00 to 21 00 OK Men...

Страница 22: ...contr OK Menu MAN OPERATION 2 Time linked circulation control illustration H ADJUSTMENTS READINGS OK PARAMETERS OK Menu storage temp limitation C time 12 00 time linked OFF circulat contr OK Menu FUNC...

Страница 23: ...ATION calorimetry illustration J ADJUSTMENTS READINGS OK col C stb C T4 C T5 C calorimetry kWh 00000 d 00000 PARAMETERS OK Menu storage temp limitation C calorimetry 1 liter puls OK OK Menu calorimetr...

Страница 24: ...ON manual operation output R1 solar loop pump solar loop pump OFF OK Menu OPERATION MAN OK solar loop pump OFF output R2 OFF MAN OK Menu OPERATION OK OK Menu MAN OPERATION solar loop pump OFF Initiali...

Страница 25: ...700676...

Отзывы: