The two top mounting holes for the 4-contact plate assembly are located above the track tube. When
drilling these two holes, use caution to ensure that the drill bit does not nick the wires located in the header
track.
c.
Using a No. 29 drill, DRILL the four mounting holes for #8-18 self-tapping screws.
d.
ROUTE the 4-contact plate wire harness to the inside of the header.
e.
Using the four screws provided, FASTEN the 4-contact plate to the header.
NOTE
The 4-contact plate must align properly with the four-contact switch block assembly on the hanger to
ensure the electrical connection to the door panel. The position of the four-contact switch block assembly
can be adjusted for vertical alignment.
3.5.3
CYCLE the door several times, and ENSURE the 4-contact switch block assembly on
the hanger leading edge mates properly with the center contact plate as the door closes.
3.6
Installing the Label (P/N: 516905)
3.6.1
INSTALL the Delayed Egress label “PUSH UNTIL ALARM SOUNDS. DOOR CAN
BE OPENED IN 15 SECONDS” in the center of the push bar. (If a 30-second egress is
required and approved by fire marshal, ATTACH the “
30
” sticker on top of the number
“
15
” in the label.)
Figure 5. Installing the 4-Contact Plate Assembly for Single-Slide Doors (Left Side Mounting Shown)
HEADER
4 CONTACT PLATE
MARK HOLES. USE # 29
DRILL
PANEL
END CAP
1.8"