Purge steam through all baler hardware nozzles to
clear condensed water and debris. Ensure nozzles are
not plugged.
7
9
11
8
10
Clean out the filter.
Re-install the filter.
Open the boiler drain valve and drain 30-40 gallons
of water. This helps prevent boil-over by reducing the
amount of dissolved solids in the boiler.
Open the supply water isolation valve. Unscrew the
supply water filter to purge any excess air that may be
trapped in the lines. Then re-tighten the filter.
Inspect gauges, sensors, and front/rear sight glasses
for damage.
Daily Maintenance (Pre-Operation)