After the OPLS trips, relieve pressure by holding the
Pressure Relief button until the OPLS resets.
If the indicators turn green for Burner Relay, Fan
VFD, and Airflow Switch, and turn red when the
Burner is turned off, they are functioning properly.
Ensure that Boiler psi 1 & 2 match the manual gauge.
Press Burner Relay then start the Water System and
Burner.
Ensure that the Fuel Pump psi number on the screen
matches the manual gauge.
You have successfully completed the Boiler Safety
Test. You can now Power Down or Continue Running.
Boiler Safety Test