Product Manual Type:
637f
07-02-10-01-E-V0304.doc
Electrical installation
5.6
Fuses, contactors, filters
Compact units
637f/ KD6R 02
.S5
KD6R 04
.S5
KD6R 06
.S5
KD6R 10
.S5
KD6R 16
.S5
KD6R 22
.S5
KD6R 30
.S5
-3
-7
-3
-7
-3
-7
-3
-7
-7
-7
-7
Fuses, Contactors
4)
RCD-switch
not recommended. Required setpoint: 300 mA, no protection against life danger
mains input currents
[A]
3,5
5
7,5
12
19
26
30
mains protection
1) mode
l
T10A T10A T10A T20A T25A
(T32A)
35A (T32A)
35A
protector-switch 2)
mode
l
PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-25 PKZ2/ZM32 PKZ2/ZM32
mains fuse
2) mode
l
DIL 00M
DIL 00M
DIL 00M
DIL 00M
DIL 0M
DIL 0M
DIL 0M
Line filters
4)
general
only for use in earth referenced supplies(TN). Current drain to PE !
single-phase
industrial env.
max. motor cable 50m
(EN55011 A)
mode
l
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
not possible
residential env.
max. motor cable 20m
(EN55011 B)
mode
l
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
not possible
3-phase
industrial env.
max. motor cable 50m
(EN55011 A)
mode
l
LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 6
LNF B 3*480/033
+
ferrite core FR 6
residential env.
max motor cable 20m
(EN55011 B)
mode
l
LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 3
LNF B 3*480/033
+
ferrite core FR 3
3-phasen, max. 3 Geräte versorgt durch einen gemeinsamen Filter
industrial env.
max. motor cable 20m
(EN55011 A)
mode
l
LNF B 3*480/018; LNF B *480/033 + ferrite core FR
other models upon request
(according to ref.measurements with 3 units, supplied by common line)
residential env.
max motor cable 20m
(EN55011 B)
3)
mode
l
LNF B 3*480/018; LNF B 3*480/033 + ferrite core FR
other models upon request
(according to ref.measurements with 3 units, supplied by common line)
Plug-in modules
637f / D6R 02
.S5
D6R 04
.S5
D6R 06
.S5
D6R 10
.S5
D6R 16
.S5
D6R 22
.S5
D6R 30
.S5
-3
-7
-3
-7
-3
-7
-3
-7
-3
-7
-3
-7
-3
-7
Fuses, contactors,
filters
4)
1)
general
Orientation: Table for compact units and the addition of rated currents of used
units on the DC-Bus. Depending on the application, energy sharing effects by
DC-link may reduce the required supply current considerable.
fuses
Rule of the thumb: single-phase operation: 2...3 times of added rated currents
Rule of the thumb: 3-phase operation: 1,5...2 times of added rated currents
peak making currents
Depending on power-supply unit, limiting equipment is requiered (delay contactor)
filters
only for use in earth referenced supplies(TN). Current drain to PE !
filter types
Orientation: Table of compact units. Further models: see separate manual
1) recommended for UL-requirements: Bussmann Type FRS-R, 600V, use only UL-approved fuse-holders !
2) recommended, Klöckner Moeller for instance
3) Measurement of conducted emissions only
4) for applications with continuous load: see notes in chapter 5.7