Product Manual Type:
637f
65
Commissioning
8.2
Commissioning in steps
Step
Action
Remark
1
Before switching on
Check the wiring, especially:
Filter polarity, supply
Motor wiring, motor polarity
Resvolver wiring,
polarity (or other feedback systems)
2
With critical mechanical part: remove motor shaft from
application
avoid danger
3
Connect PC by RS232 link to the drive service port COM1
and start EASYRIDER
®
Set up state
NOT ACTIVE
635/ 637/ 637+/ 637f
1)
X10.22 against X10.9
631
X10.7 against X10.4
4
Power on
7-segment-
dispay
Switch on control voltage
635/ 637/ 637+/ 637f
Us = 24V DC
631
Us = 230V AC
5
EASYRIDER
®
communicates (see diagnosis F9)
7-segment-
dispay
Are parameters already evaluated?
6
Yes:
load parameter-file
xxx.WDD.
Store parameters in the
drive. If existent: load BIAS-
file xxx.WBD and store in
drive.
Proceed with
10 or 15
(experts)
No:
continue with
7
7
Menu Commissioning:
Select the used motor from the EASYRIDER
®
- Library
Adjust max. current to nominal motor current or smaller
reduced torque
8
When leaving that menu:
Tuning-parameters for current loop will be calculated and
offered to the user.
Normally, these values give dynamic servo motion.
Confirm acceptance of offered
parameters
9
Store data power-fail-save in the drive
10
Menu: Tuning speed loop
1)
Hint:
With the assembly of the option module SBT you kindly note the extended functions of the
signals (see documentation 07-02-10-02-E..)