IM-P198-02
MI Issue 5
84
8.5 Calibrating Analog Input and Output in the LCD
Calibration of analog input and output from the LCD interface is done through the Service
menu.
To get to the Service menu:
1.
Go into programming mode by holding the magnet over the Enter button for
approximately five seconds.
2.
Using the down arrow, scroll down to the Calibrate 4-20 line item.
3.
Select it with the Enter button. This will take you to the Select Channel screen. You
will be able to scroll through three input and three output settings. These settings will
determine two points; the bottom end and the top end of the input and output currents.
4. Select the Cal ch 1 output line item and select it. The first screen will show you how to
connect the terminals.
8.5.1 Output calibration:
5.
When the terminals have been connected as indicated, select Next for the following
screen.
6.
This screen will show 'Output now set to approx. 3.47 mA.'
7.
Confirm that your low end output is set as close as possible to this number.
8.
Select the bottom navigation bar to go to the next screen.
9.
'Enter measured current message' will scroll across the screen.
10.
Select Edit in the navigation bar to enter edit mode. The cursor will blink over the last
number.
11.
Use the left and right arrow keys to move around within the number displayed. Use the
top and bottom arrow keys to increase or decrease each number until it is set to the
correct mA.
12.
Select the Enter button to save, then select Next.
13.
The screen will now show 'Output now set to approx. 21.50 mA.'
14.
Confirm that your high end output is set to approximately this number.
Fig. 95