IM-P198-02
MI Issue 5
21
3.3.4 Rotor orientation and final positioning
Caution:
Do not force the stem into the pipe. If the stem insertion is blocked, retract and
remove the flowmeter from the pipeline, checking to make sure the opening conforms with
the guidelines listed in the mounting guidelines.
Manually insert the stem into the pipe until the calculated insertion depth is obtained. Align
the rotor by using the orientation levers so that the flow direction arrow is parallel to the
pipe and pointed downstream.
Lock the stem in position by tightening the Swagelok
®
fitting. Verify insertion depth prior
to final tightening of the fitting. When the fitting has been tightened, the stem position
becomes permanent and cannot be changed.
3.4 Remote mounting of the electronics
The RIM10 flowmeter electronics condulet can be remotely mounted using the pipe mount
or wall mount options.
Cable and 'U' bolts are supplied with the mounting plate. A maximum of 30.5 m (100 ft) of
cable can be used. Cable must be run in conduit (not supplied). Conduit connections are
18 mm (¾").
Fig. 16 Wall mount electronics
Fig. 17 Pipe mount electronics
139.7 mm
(5.5")
150 mm
(6")
165.1 mm
(6.5")
215.9 mm
(8.5")
139.7 mm
(5.5")
4 x 7.14 mm
(0.281")
10.2 mm
(0.4")
7.14 mm
(0.281")
127 mm
(5")
106.7 mm
(4.2")
215.9 mm
(8.5")
195.6 mm
(7.7")