IM-P198-02
MI Issue 5
56
5.28 Service
(factory settings)
This menu (Figure 59) lets a qualified
service technician reset the non-
resetable totalizers.
5.27 Service
(outputs test)
This menu (Figure 58) lets the user
test the 2 relay alarms and the pulse
output.
Main Menu
Return to Display
Reset Totalisers
Reset Min / Max
Display Set-up
Set-up Wizard
Network Set-up
Set Time / Date
Faults
Service
Enter / right
arrow
Service Menu
Reset Password
Calibrate 4-20
Outputs
Factory
Enter / right
arrow
Output tests
Relay 1 Test
Relay 2 Test
Pulse Output Test
Main Menu
Return to Display
Reset Totalisers
Reset Min / Max
Display Set-up
Set-up Wizard
Network Set-up
Set Time / Date
Faults
Service
Enter / right
arrow
Service Menu
Reset Password
Calibrate 4-20
Outputs
Factory
Enter / right
arrow
Select Totaliser
# 1 Non-resetable
# 2 Non-resetable
Factory password :
0 0 0 0 0 0
EDIT
Enter / right
arrow
The Relay tests close the selected relay for
3 seconds.
The Pulse Output Test produces a 500 ms
square wave for 2 seconds.
The factory
password is only
for authorised
service personnel
After the
correct password
is entered.
Fig. 58
Fig. 59