IM-P198-02
MI Issue 5
28
4.2.6 Relay output
There are 2 single pole double throw relays available. Each has a normally-closed and
normally-open contact which can be wired as shown in Figures 25 and 26. These relays
provide resistance of 35 ohms maximum and switching times of less than 1 millisecond.
They are limited to 120 mA of current and 350 V blocking voltage. The maximum current and
voltage in hazardous environments is 50 mA and 24 V.
An alternate view of the relay contacts is shown below:
Fig. 25
Fig. 26
RIM10 terminal
10
Relay 1 Normally-closed contact
11
Relay 1 Pole
12
Relay 1 Normally-open contact
22
Relay 2 Normally-closed contact
23
Relay 2 pole
24
Relay 2 Normally-closed contact
RIM10 terminal
10
Relay 1 Normally-closed contact
11
Relay 1 Pole
12
Relay 1 Normally-open contact
22
Relay 2 Normally-closed contact
23
Relay 2 pole
24
Relay 2 Normally-closed contact
Relay outputs
Relay outputs