8.4 Flowmeter faults menu
When the fault LED turns on, details of the problem can be viewed using the LCD interface:
1.
Hold the magnet over the Enter button for five seconds to enter programming mode.
2.
Using the magnet with the down arrow, scroll to the Fault line item. When selected, a
screen will appear displaying how many faults there are.
3.
Select Enter to see a list and use the arrow keys to scroll through and view the faults.
4.
Once a fault has been corrected, the fault list on the LCD interface must still be cleared.
To clear a fault, scroll down to the Clear bar at the bottom of the LCD screen. Select Enter
to clear that error.
In cases where there are two or more faults at one time, it is suggested that each fault be
corrected and then cleared individually rather than all at once.
Error Code
Description
00
Substitute values in use
01
Relay 1 Alarm
02
Relay 2 Alarm
03
Meter powered down
04
Pulse out queue full, pulses lost
05
4-20 Analog output 1 out of range
06
4-20 Analog output 2 out of range
07
4-20 Analog output 3 out of range
08
4-20 Analog input temperature 1 out of range
09
4-20 Analog input temperature 2 out of range
10
Open circuit on internal RTD sensor
11
Open circuit on external RTD sensor
12
4-20 Analog input pressure out of range
13
adc input voltage exceeded conversion range
14
Internal clock failed, time stamps inaccurate/wrong
15
RAM failed to read correct value after write
16
Configuration data checksum fault
17
Flash memory checksum fault
18
Insertion Vortex sensor disconnected
19
Velocity below minimum
20
Velocity above maximum
21
Keypad fault,
22
Web server is down
23
Modbus server is down
24
Flow calculator is down, flowmeter is not functional
25
Data acquisition is down, flowmeter is not functional