Series 200 IR Gas Detector - User’s and Maintenance Manual
Doc. No. TM792100, Rev. B, Oct..1997
- 24 -
mounted in a position where it cannot be knocked out of alignment, or guarded from
physical impact.
2. 2. 4.
Unpacking
1. Upon receipt, verify the appropriate Purchase Order and record the Part
Number and Serial Number of the Source and Detector units in the appropriate
Log Book.
2. Carefully unpack the following equipment observing any instructions printed on
or contained in the packaging list. Check the contents for any possible damage
caused from shipping and handling. In the event of damage or loss in transit,
notify the carrier and your Supplier immediately.
The System should include the following (in addition to this manual):
•
Detector unit
•
Source unit
•
Two Swivel Mount Bases. One unit is used for the Detector and one unit is
used for the Flash Source.
•
Telescope Kit
•
Calibration Filter
•
Magnetic Mode Selector
Notes:
1. The Magnetic Mode Selector, the Calibration Filter and the Telecope Kit
are used during each detector’s installation and then removed. They can be
reused for all other detectors’ installation in the site.Therefore, only one set
is submitted for several detectors.
2. There are two different Telescope Kits:
-
For standard installation -
P/N 794110 ( see Figure 3-2, items 1-5)
-
For Duct installation -
P/N 794245 (see Figure 2-5)
2. 3. Mounting for Standard Installation
The following instructions are applicable for both the Flash Source unit and the
Detector unit.
The detector may be mounted on special Swivel Mount. The Swivel Mount enables
the detector to be rotated up to 30 degrees in all directions and fine alignment of up to
3 degrees.
Note:
For Aluminium and St.St. detector enclosure use Swivel Mount P/N 794765 for
inches measure or P/N 794765-1 for metric measure. The Swivel Mounts models are
made of St.St. 316.