1. 10. System Setup
1. 10. 1.
Detector Setting
The detector consists of the following DIP Switches which enable the user to adapt
the detector operation to specific application:
SW1 - Function Selection Switch. Contains. 8 DIP Switches. Used for Calibration of
different gas selection, response time control and Relays response
configuration.
SW2 - Address Selection Switch. Contains 8 DIP Switches. Used for Detector’s
address setting and 4-20mA output configuration setting.
SW3 - Alarm Options Selection Switch. Contains 4 DIP Switches. Used for
Detector’s Alarm Latching configuration and 4-20 mA level reading
configuration.
Function Selection Switch:
Table 1-7 describes SW1 DIP Switches position and the required function for setting
the detector. according to the necessary configuration
Table 1-7. SW1 DIP Switches Configuration
Switch
No.
off position
on position
Default
setting
1.
Detection speed control bit 0 at “0”
(see note 1 below)
Detection speed control bit 0 at “1”
(see note 1 below)
on
2.
Detection speed control bit 1 at “0”
(see note 1 below)
Detection speed control bit 1 at “1”
(see note 1 below)
off
3.
Gas type control bit 0 at “0
(see note 2 below)”
Gas type control bit 0 at “1”
(see note 2 below)
off
4.
Gas type control bit 1 at “0
(see note 2 below)”
Gas type control bit 1 at “1”
(see note 2 below)
off
5.
Full scale sensitivity is 0-5 LEL
x
m
Full scale sensitivity is 0-2 LEL
x
m
off
6.
Zero calibration is performed
according to background
Gas level detection performed without
background Zero calibration
off
7.
Accessory Relay is activated at
Warning level
Accessory Relay is activated at Alarm
level (with the Alarm Relay)
off
8.
Accessory Relay is activated
according to SW1-7 position
Accessory Relay is Activated at Power
on continuously ( used as End of Line)
off
Notes:
1.
Detection flashes rate can be selected by pre-setting of SW1-1 and SW1-2
according to the following table. There are two bits which provides four Flash
Source rates. Same Flash rate should be set also at the Flash Source.
Table 1-8. Flash Source Flash Rate Configuration
bit #0 position
(SW1-1)
bit #1 position
(SW1-2)
Source flash Rate
(flashes/second)
off
off
0.5
on
off
1
off
on
2
on
on
4