SafEye
™
™
Series 200 IR Gas Detector - User’s and Maintenance Manual
SPETCREX INC.
Doc. No. TM792100, Rev. B, Oct 1997
- 25 -
2. 3. 1.
Swivel Mount Kit
The Swivel Mount Kit includes the items listed in Table 2-1 as follows:
Table 2-1. Swivel Mount Kit
ITEM
QTY
LOCATION
Swivel Mount
1
Screw 1/4”-20UNC or M6 x 1P
4
Detector - Holding plate
1/4” Spring Washer
4
Detector - Holding plate
2. 3. 2.
Swivel Installation (Figure 2-1)
1. Place the swivel mount Securing Plate (2) in its designated location and secure
it with four M6 or 1/4”-20UNC screws (9), placed 76.2 mm. (3 in.) apart.
Note: Skip this step if the Swivel Mount is already installed. Also detector
removal for maintenance purpose does not require Swivel Mount
removal.
2.
Unpack the detector carefully
3.
Place the detector with its conduit inlets pointing down on the holding plate of
the swivel mount (10). Secure the detector by four 1/4”-20UNC allen screws or
M6 x 1P (8) with 1/4” spring washers from the swivel mount kit (use No. 5 Hex
Key for M6 screws, or 3/16” Hex Key for 1/4”-20UNC screws).
4.
Tighten the three locking 3/8”-24UNF screws (5) of the swivel mount ring until
the friction in the ball joint holds the detector in its position. Yet, still permits it
to be moved by hand-applied force (use 3/16 Hex Key).
5.
Point the detector towards the Flash Source and make certain that the view of
the area is not obstructed. Secure the detector in that position by tightening the
locking screws of the swivel mount ring.
6.
Repeat mounting and Swivel Mount installation described in this chapter for
installing the Flash Source.
The detector is now correctly located and ready for the electrical connecting to the
system prior to fine alignment.