2. 6. Flash Source Wiring
2. 6. 1.
Power Supply
Input power is supplied to terminal 1. The return is connected to terminal 2 (see
figure 2-10).
Note:
Ensure that the Flash Source unit will receive a
minimum of 18 Volts DC and does not exceed
32 Volts DC.
Pre-wiring requirements and wiring requirements are identical to the appropriate
requirements for the detector, as described in section 2.5.1.
2. 6. 2.
Harness Connection (Figure 1-6)
The instructions for this are identical to the detector. Refer to section 2.5.2
2. 6. 3.
Terminal Wiring (Table 1-6)
The Flash Source contains a terminal board. Terminal Wiring Instructions are identical
to the Detector Wiring instructions. The Flash Source consists of two wires only. The
Positive supply power connected to terminal 1, and the common return connected to
terminal 2.
Connect the Grounding Cable to the Ground Terminal (4) outside the Flash Source
cover (2). The detector must be well grounded to Earth Ground for proper operation.