SafEye
™
™
Series 200 IR Gas Detector - User’s and Maintenance Manual
SPETCREX INC.
Doc. No. TM792100, Rev. B, Oct.. 1997
- 49 -
Example:
At a hypothetical installation the LEDs are Green-Orange with 3 green blinks (left
LED) and 6 orange blinks (right LED).
The number is 36 + 124 = 160
The next periodic maintenance reading has Orange-Orange LEDs with 8 orange blinks
(left LED) and 8 orange blinks (right LED).
The number is 88 + 62 = 150
The variance is 160-150 =
10 Units
The percentage of variance will be (10/160)*100 = 6.25% less then previous
alignment.
4. 2. 3.
Calibration Check
1. Clean the optical surfaces (see section 4.2.1).
2. Perform the signal intensity check (see section 4.2.2).
3. Perform the calibration check (see section 3.5).
4. 2. 4.
Maintenance Records
Record every maintenance operation performed on the Source and/or Detector in a
Maintenance Records Log-book. The records should include but not be restricted to
the following:
•
The information identifying the measurement units.
•
The date of installation and contractor.
•
Entries for every maintenance operation performed to include at least the
description of the operation, date and personnel ID.
•
Signal intensity records with SIC results.
•
Calibration check (CC) results.
If the unit(s) is (are) sent to the authorized Supplier, a copy of the Maintenance
Records must accompany the unit concerned.