Series 200 IR Gas Detector - User’s and Maintenance Manual
Doc. No. TM792100, Rev. B, Oct..1997
- 44 -
4.
Detector Crude Alignment:
Refer to Figure 3-2 for all the following instructions.
a.
Use 3/16” Allen screwdriver to loosen up the 3 socket set screws (7).
b.
Tilt the Flash Source to the general direction of the Detector.
c.
Rotate the Periscope (4) until its ocular is positioned in front of your
aiming eye for most convenient observation.
d.
Observe through the Periscope (4) and locate the Detector in the center of
view.
e.
Tighten three socket set screws (7) of the Detector’s Swivel Mount.
5.
Release the Fastening Screw (3) and remove the Telescope from the Detector.
6.
Flash Source Crude Alignment
Repeat Steps 3 through 4 for the Flash Source.
7.
Flash Source Fine Adjustment:
a.
Release the Adjustment Screw Securing Nuts (10) from all Adjustment
Screws (8,9) to enable fine alignment.
b.
Watch through the Periscope(4). The cross midpoint inside the Telescope
Lens should be aimed to the opposite unit (Flash Source) such that it is
observed in the Periscope.
c.
Rotate the Vertical Adjustment Screws (8) and the Horizontal Adjustment
Screws (9). This should be performed until the cross midpoint is
combined with the center of the top of the Flash Source Telescope Sight
Mounting (Figure 3-2, item 2).
d.
Carefully secure the four Adjustment Screw Securing Nuts (10).
e.
Release the Fastening Screw (3) and remove the Telescope(1) from the
unit.
8.
Detector Fine Adjustment
Repeat Steps 3 and 7 for the Detector.
9.
Repeat steps 3,7 and 8 if additional Adjustment is required.
10.
Upon alignment completion perform the following:
a.
Reinstall Protective Sight Covers of the Detector and the Flash Source by
screwing four Sight Cover screws (Figure 3-1, item 6).
b.
Return the Telescope in its Original case.
11.
Power on the system according to section 3.3.
12.
Perform zero calibration according to section 3.4.
13.
Perform Signal Intensity Check (SIC) according to section 4.
14.
Perform Calibration Check (CC) according to section 3.5.