SafEye
™
™
Series 200 IR Gas Detector - User’s and Maintenance Manual
SPETCREX INC.
Doc. No. TM792100, Rev. B, Oct 1997
- 7 -
•
Low Voltage Fault
In this case detection is disabled due to low voltage supplied to the detector. The
detector returns to proper operation only when proper voltage level restores.
1. 6. 2.
Alignment Mode
This mode is used when the received signal needs to be measured (i.e. Installation &
Periodic Maintenance). LED indications represent the received signal for precise
alignment. There is a temporary Standby Mode to give the option of switching from
Alignment Mode to Calibration Mode.
1. 6. 3.
Calibration Mode
This mode zeros the gas detection reading . It should only be performed when there
is no combustible gases (or insignificant) blocking between the Flash Source and
Detector units, and in proper weather conditions. After calibration the detector
switches to Normal Mode.
1. 6. 4.
Mode Selection
A Magnetic Mode Selector is used to change to alignment and calibration modes by
placing the magnet on the side of the detector .