![Sony MG40 Series Скачать руководство пользователя страница 102](http://html.mh-extra.com/html/sony/mg40-series/mg40-series_command-reference-manual_411003102.webp)
4-14
(E)
MG40 Series
Comparator group number
Th
is function is used to select and acquire the comparator group number to be used.
Set
Setup
mode
Ethernet
CC-Link
Measurement
mode
The command sets the comparator group number to be used.
Command format
CMS Designated axis =<Group number>
<Group number>
01 : Comparator group number 01 (Factory setting)
02 : Comparator group number 02
.
.
.
16 : Comparator group number 16
Return format
Execution results
Target
Designated axis, MG42 hub unit, all axes
Save setting values
Setting values saved.
Examples of use
Transmission :
CMS[01B]=05
(Set the comparator group number for axis B for the
MG42 hub unit ID01 to 5.)
Return
:
OK000
(Successfully
completed.)
Compatible command
Designated axis SCN=<Group number>
Acquire
Setup
mode
Ethernet
CC-Link
Measurement
mode
The command acquires the comparator group number which has been set.
Command format
CMS Designated axis ?
Return format
CMS Designated axis =<Group number>
<Group number>
01 : Comparator group number 01
02 : Comparator group number 02
.
.
.
16 : Comparator group number 16
Target Designated
axis
Examples of use
Transmission :
CMS[00A]?
(Acquire the comparator group number for axis A for
the MG41 main unit.)
Return
:
CMS[00A]=16
(Th
e group number is 16.)
Compatible command
None
Содержание MG40 Series
Страница 2: ...MG40 Series ...
Страница 4: ...ii J MG40 Series ...
Страница 8: ...1 4 J MG40 Series ...
Страница 20: ...3 4 J MG40 Series ...
Страница 68: ...5 6 J MG40 Series ...
Страница 72: ...ii E MG40 Series ...
Страница 76: ...1 4 E MG40 Series ...
Страница 88: ...3 4 E MG40 Series ...
Страница 136: ...5 6 E MG40 Series ...