77
J-D
Additional timings
A
Sum, reset time
07:00:00
B
Occasional storage interval
00:01:00
C
Sync date (last)
D
Sync time (last)
E
min. Hold on message
5
min
F
max. Hold on message
0
min
G
Hold commander
8
sec
H
Main Switch reset
off
I
Logger reboot time
J-D-A
Sum, reset time
Time at which the sums of summed variables defined in
Value range
Default
Unit
00:00:00 … 23:59:59
07:00:00
-
J-D-B
Occasional storage interval
Storage interval of variables which are only stored at the time when their value changes. Counter var-
iables and certain system variables are stored by default in this interval. By adding the command
SY
, the variable is forced to be stored in the primary storage interval.
Value range
Default
Unit
00:00:00 … 23:59:59
00:01:00
-
J-D-C
Sync date (last)
The date at which the MRL-7 date is manually synchronized to the Commander date; read only. This
date is saved automatically for traceability.
J-D-D
Sync time (last)
The time at which the MRL-7 time is manually synchronized to the Commander time; read only. This
time is saved automatically for traceability.
J-D-E
min. Hold on message
The time, after a limit violation, for which a message or switch action is valid. For example, if a value
of five minutes is entered, and the wind speed of a connected anemometer exceeds the limit value
repeatedly within these five minutes, no additional message is sent. Used to suppress multiple mes-
sages if variable fluctuates around the limit value.
Value range
Default
Unit
0 … 180
5
min