8
Copyright © 2014 SOMFY ACTIVITES SA. All rights reserved.
EN
Rollixo RTS
6 - USER TRAINING
Train all uses in how to safely use this motorised door (standard use and
locking principle) and on the mandatory periodic checks.
7 - CONNECTING ADDITIONAL DEVICES
7.1 General wiring diagram
L1
L2
N
M
1
2
3
4
24 Vdc
Antenne
R
24V dc
24V Cell
Ant
Sec Cell
Sec
Safety Edge
Stop
KeySwitch
Test
Sec
Flash
5
6
7
8
9
10
11
12
13
16
17
18
19
20
22
14
15
Aerial
24 Vdc
Terminal Type of
terminal
Connection
Comments
1
Earth
RDO CSI 50 or 60
motor
2
L1
3
Neutral
4
L2
5
Contact
Fall protection - NC
contact
6
Shared
7
Contact
Safety edge safety
input
Wired 8k2 resistive safety
edge (terminals 7 - 8)
Wired optical safety edge
(terminals 7 - 8 - 9)
8
12 Vdc
12 Vdc safety edge
power supply
9
0 Vdc
10
Contact
NO contact
Sequential control
11
Shared
12
24 Vdc
24V - 3.5 W orange
light output
Maximum 4 W bulb
13
0 Vdc
14
24 Vdc
TX cell 24 V power
supply
Transmitting photoelectric
FHOO5HÀH[SKRWRFHOO
power supply
15
0 Vdc
16
24 Vdc
RX cell 24 V power
supply
Receiving photoelectric
cell power supply
17
0 Vdc
18
Shared
19
Contact
Cell safety input (NC)
20
Test output
Cell safety test output
5HÀH[SKRWRFHOOVHOIWHVW
22
433.42 MHz aerial
Do not connect an offset
aerial (incompatible)
7.2 Parameter setting for wiring options
Dipswitch
Possible parameter
setting
ON
OFF
1
Cell self-test
Activated
Deactivated
2
Choice of cell type
Photoelectric
Electric eye
3
Orange light 2s
warning
Activated
Deactivated
4
Choice of wired safety
edge type
Resistive
Optical
5
Holiday mode parameter setting (see section 8.4)
6
Do not use
3
4
2
1
Prog
STOP
7.3 Description of the various additional devices
> Photoelectric cells
WARNING
N.B.: In accordance with standard EN 12453 governing the safe use
of motorised gates and doors, the use of the TAHOMA control box to
automatically control a garage door or gate not visible to the user requires
the installation of a photoelectric cell type safety device with autotest on the
automatic control system.
Receiver
Comments
Dipswitch 1 Dipswitch 2
Without auto-
test
OFF
ON
Requires checking for
correct operation every 6
months.
With auto-test
ON
ON
Enables an automatic
test to be carried out to
check the operation of the
photoelectric cells each time
the door moves.
If the operational test is
negative, closure is in
downgraded mode (press
and hold down ).
WARNING
It is compulsory to install photoelectric cells if:
- the automatic control device is being controlled remotely (user unable to see it),
- automatic closure is activated.
If cells are removed, it is essential to create a bridge between
terminals 18 and 19.
1
2
14
15
17
TX
RX
1
2
3 18
16
5 19
TX
RX
24V dc
24V Cell
Sec Cell
Test
Sec
h
16
17
18
19
20
14
15
Содержание ROLLIXO RTS
Страница 1: ...ROLLIXO RTS 3 4 2 1 Prog STOP Installation manual Instrukcja monta u Manual de instalaci n EN PL ES EL...
Страница 2: ......
Страница 48: ...2 Copyright 2014 SOMFY ACTIVITES SA All rights reserved EL Rollixo RTS 1 3 1 4 5 2 6 1 5 P N9 1 6 P PP...
Страница 62: ......
Страница 63: ......