51
June 2020
|
Solar Stik
®
, Inc.
SYSTEM SETUP AND OPERATION GUDIE FOR THE 1 kW HYBRID POWER SYSTEM (HPS)
PRELIMINARY DRAFT
GROUP 3: INPUT LOW LIMIT
Parameter
Setting Value
Description
RESET VOLTAGE
105.0 V
This is the reset voltage at which the PRO-Verter will revert to Charging
mode after it has switched over to Inverting mode due to input voltage
falling to Cut Off Volt 1/Cut Off Volt 2/Cut Off Volt 3.
CUT OFF VOLT 1
100.0 V
If during Charging mode, the AC input voltage falls below Cut Off Volt 1 for
period > Detect Time 1, the PRO-Verter will transfer to Inverting mode from
Charging mode.
DETECT TIME 1
300 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off Volt
1 is allowed.
CUT OFF VOLT 2
95.0 V
If during Charging mode the AC input voltage falls below Cut Off Volt 2 for
period > Detect Time 2, the PRO-Verter will transfer to Inverting mode.
DETECT TIME 2
60 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off 2 is
allowed.
CUT OFF VOLT 3
90.0 V
If during Charging mode, the AC input voltage falls below Cut Off Volt 3 for
period > Detect Time 3, the PRO-Verter will transfer to Inverting mode.
DETECT TIME 3
1 Cycle
This is the time limit in cycles up to which the low AC input voltage Cut Off
3 is allowed.
Input Low Limit Programmable Settings
Table 6. Parameters for Grid/Generator Input Low Voltage Level
GROUP 4: INPUT HIGH LIMIT
Parameter
Setting Value
Description
RESET VOLTAGE
125.0 V
This is the reset voltage at which the PRO-Verter will revert to Charging
mode after it has switched over to Inverting mode due to input voltage
falling to Cut Off Volt 1/Cut Off Volt 2/Cut Off Volt 3.
CUT OFF VOLT 1
135.0 V
If during Charging mode the AC input voltage falls below Cut Off Volt 1
for period > Detect Time 1, the PRO-Verter will transfer to Inverting mode
from Charging mode.
DETECT TIME 1
60 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off
Volt 1 is allowed.
CUT OFF VOLT 2
140.0 V
If during Charging mode the AC input voltage falls below Cut Off Volt 2 for
period > Detect Time 2, the PRO-Verter will transfer to Inverting mode.
DETECT TIME 2
15 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off
Volt 2 is allowed.
CUT OFF VOLT 3
145.0 V
If during Charging mode the AC input voltage falls below Cut Off Volt 3 for
period > Detect Time 3, the PRO-Verter will transfer to Inverting mode.
DETECT TIME 3
1 Cycle
This is the time limit in cycles up to which the low AC input voltage Cut
Off Volt 3 is allowed.
Input High Limit Programmable Settings
Table 7. Parameters for Grid/Generator Input High Voltage Level