SYSTEM SETUP AND OPERATION GUDIE FOR THE 1 kW HYBRID POWER SYSTEM (HPS)
PRELIMINARY DRAFT
h How to Set GRID MAX CURRENT equal to connected generator
or grid output current
Set the “Grid Max Current” setting to the same value (up to 20 A; max setting) as the maximum
continuous output current of the AC power source (grid or generator) connected to the PRO-Verter.
This setting is required to optimize generator/PRO-Verter interactions and System performance. If
the PRO-Verter current setting is greater than the power source, the source will be overloaded and
fault. If the PRO-Verter current setting is lower than the power source, System performance will be
reduced or not be able to support loads that fall within the rated performance of the PRO-Verter.
Consult table on the PRO-Verter S 2000 I-Plate for recommendations on setting the AC INPUT when
connected to a Ranger/Defender MPG.
Select Group
CHARGE CURVE
Select Group
INPUT SETTING
EVO-1224
AC output:
Standby
120.0V
<0.1 A
60.00Hz
*
*
Select Parameter
INPUT SETTING
DEFAULT FREQ
0=60Hz
Select Parameter
INPUT SETTING
GRID MAX CURRENT
6.5A
*
*
“Input Setting”
Home Screen
Set GRID MAX CURRENT equal to connected generator or grid output current
1. Press ENTER button.
2. Press DOWN button to arrive at INPUT SETTING.
3. Press ENTER button.
4. Press DOWN button to arrive at GRID MAX CURRENT.
5. Press ENTER button and hold until number flashes.
6. Press UP or DOWN button to change number.
7. Press ENTER to move to next digit.
8. When correct value is entered, press and hold ENTER to save.