the red light will be on, and the fault can be found in the history of the fault. For
the machine installed with Wi-Fi/GPRS, the alarm information can be seen on
the corresponding monitoring website, and can also be received by the APP on
the mobile phone.
Table 7-1 Event list
Code
Name
Description
Solution
ID001
Grid OVP
The grid voltage is too
high
If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal occasionally. Inverter will
automatically return to normal operating
status when the electric grid’s back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within
the acceptable range. If yes, please check
the AC circuit breaker and AC wiring of the
inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
contact technical support to change the grid
over-voltage, under-voltage,
over-frequency, under-frequency protection
points after obtaining approval from the
local electrical grid operator.
ID002
Grid UVP
The grid voltage is too
low
ID003
Grid OFP
The grid frequency is
too high
ID004
Grid UFP
The grid frequency is
too low
ID005
GFCI
Charge Leakage Fault
Check for inverter and wiring.
ID006
OVRT fault
OVRT function is
faulty
If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal occasionally. Inverter will
automatically return to normal operating
status when the electric grid’s back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within
the acceptable range. If yes, please check
the AC circuit breaker and AC wiring of the
inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
contact technical support to change the grid
over-voltage, under-voltage,
over-frequency, under-frequency protection
points after obtaining approval from the
ID007
LVRT fault
LVRT function is faulty
ID008
Island Fault
Island protection error
ID017
HwADFaultIGrid
Power grid current
sampling error
ID018
HwADFaultDCI
Wrong sampling of dc
component of grid
current
ID020
HwADFaultVGri
d(AC)
Power grid voltage
sampling error (AC)
ID022
GFCIDeviceFault
(AC)
Leakage current
sampling error(AC)