SOFAR 7K~10.5KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 27 -
4.4. Connecting AC Output Power Cables
Connect the SOFAR 7K~10.5KTLM-G3 to the AC power distribution frame or
power grid using AC output power cables.
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit breaker.
AC breaker used as disconnect device, and the disconnect device shall
remain readily operable.
Caution
Context
SOFARSOLAR has already integrated RCMU (residual current monitoring unit)
inside inverter, If an external RCD is required, a type-A RCD with rated residual
current of 100mA or higher is suggested. Please check with the local regulation
for the sizing of rated residual current.
All the AC output cables used for the inverters are outdoor three-core cables. To
facilitate the installation, use flexible cables. Table 4-2 lists the recommended
specifications for the cables.
Figure 4-8 NOT allowed: connect loads between inverter and circuit breaker
Table4-2 Recommended AC output cable specifications
Model
7KTLM-
G3
7.7KTLM-
G3
8KTLM-
G3
9KTLM-G
3
10KTLM
-G3
10.5KTLM
-G3
Cable
(Copper)
≧
6mm²
≧
6mm²
≧
6mm²
≧
10mm²
≧
10mm²
≧
10mm²
Breaker
60A
60A
60A
100A
100A
100A
Note:
The rated power of the meter must be greater than the maximum power of